Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/19/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/17/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210*/DENIED 1)PLEASE EXPOSE THE ENDS OF THE GROUND RODS FOR INSPECTION. NEW SERVICE-NEW GROUNDING REGDIE? 2)NEC ART 380-8 PROHIBITS CIRCUIT BREAKERS BE MOUNTED HIGHER THAN 6'-7" FROM NATURAL GRADE. 3)JUMPER FROM COLD WATER PIPE TO HOT WTR. PIPE AT WATER HEATER. THIS IS BECAUSE THE PIPING SYSTEMS ARE ISOLATED BY DIELECTRIC UNIONS AT THE WATER HEATER. 4)REMOVE ROMEX AT FRONT OF HOUSE. IT IS AN ILECTRICAL HAZARD. |