Permit: T04EL01656

Parcel: 140060950


Addresses:

3714 E FRANKFORT SV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04EL01656

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/23/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/16/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :INSTALL BUSHING WHERE ROMEX EXITS 3/4" CONDUIT TO PROTECT CABLE FROM ABRASION
SERVICE UPGRADE PARTIAL APPROVAL, HOWEVER INSPECTOR NOTICE OTHER WIRING THAT IS UNSAFE AND NEEDS REPAIRED ASAP
(A) WIRING BY COOLER HAS EXPOSED NON UF ROMEX AND SPREADER BOX NOT ALLOWED PER NEC
(B) SPLICES SHOULD BE IN APPROVED J-BOXES ALSO UNDER ROOF OVERHANG EAST SIDE, WIRING ANF LIGHT FIXTURES, SPLICED EXTENSION CORDS
(C) WIRING IN WASHER/DRYER AREA UNSAFE