Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04EL01656
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/23/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/16/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :INSTALL BUSHING WHERE ROMEX EXITS 3/4" CONDUIT TO PROTECT CABLE FROM ABRASION SERVICE UPGRADE PARTIAL APPROVAL, HOWEVER INSPECTOR NOTICE OTHER WIRING THAT IS UNSAFE AND NEEDS REPAIRED ASAP (A) WIRING BY COOLER HAS EXPOSED NON UF ROMEX AND SPREADER BOX NOT ALLOWED PER NEC (B) SPLICES SHOULD BE IN APPROVED J-BOXES ALSO UNDER ROOF OVERHANG EAST SIDE, WIRING ANF LIGHT FIXTURES, SPLICED EXTENSION CORDS (C) WIRING IN WASHER/DRYER AREA UNSAFE |