Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04EL01656

Parcel: 140060950


Addresses:

3714 E FRANKFORT SV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/23/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/16/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :INSTALL BUSHING WHERE ROMEX EXITS 3/4" CONDUIT TO PROTECT CABLE FROM ABRASION
SERVICE UPGRADE PARTIAL APPROVAL, HOWEVER INSPECTOR NOTICE OTHER WIRING THAT IS UNSAFE AND NEEDS REPAIRED ASAP
(A) WIRING BY COOLER HAS EXPOSED NON UF ROMEX AND SPREADER BOX NOT ALLOWED PER NEC
(B) SPLICES SHOULD BE IN APPROVED J-BOXES ALSO UNDER ROOF OVERHANG EAST SIDE, WIRING ANF LIGHT FIXTURES, SPLICED EXTENSION CORDS
(C) WIRING IN WASHER/DRYER AREA UNSAFE