Permit: T04EL01652

Parcel: 107030500


Addresses:

1926 W GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/10/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* OK TO CLEAR
09/21/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
NO ONE HOME SIDE GATE OPEN
1) SERVICE MUST BE PERMANENTLY ADDRESSED 2) NEW WIRING PULLED INTO SERVICE MUST BE PERMITTED. 3) NEW SERVICES REQUIRE 2 GROUND ?? WATER & GAS BOND. A) WATER LINE BOND CONNECTED TO AN UNUSED SECTION B) GAS LINE BOND TO BE ON HOUSE SIDE OF UNION. 4) HOLES UNDER SERVICE TO BE SEALED, USE A ROMEX TO SEAL 1/2" HOLE WHERE GROUND WIRE EXITS.