Permit: T04EL01640

Parcel: 113031000


Addresses:

909 E KING ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/09/2004 ELECTRIC - SERVICE UPGRADE Approved OK TO CLEAR
09/03/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The service is not per code.| 210*/1)THERE MUST BE A PIPE STRAP ON THE RISER PIPE WITHIN 8" OF THE TOP OF THE BOX.
2)MARK/IDENTIFY WHAT THE CIRVUIT BREAKERS SERVE (E.Q. SUB PANEL-DRYER ETC.)
3)UNABLE TO INSPECT GROUNDING-LOOSE DOGS IN YARD
RECALL WHEN CORRECTIONS COMPLETE & DOGS ARE SECURED