Permit: T04EL01633

Parcel: 124070690


Addresses:

723 E FLORITA ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/16/2004 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :* BE ADVISED, THE NEW SERVICE TO EXISTING SWITCH_ THE COLOR RED IS RESERVED FOR CURRENT CARRYING CONDUCTORS ( HOT) REPLACE WITH WHITE CONDUCTOR AND INCLUDE A GREEN CONDUCTOR TO GROUND THE STEEL OF THE SWITCH WITH THE STELLOF THE NEW PANEL. CHANGE PIPE OT 3/4 ". CALL FOR FINAL INSPECTION WHEN COMPLETE
08/13/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The service entrance is not per code.| 215* 1) YOUR GROUNDING CIRCUIT IS UNACCEPTABLE. THE ELECTRICAL CODE REQUIRES THE PRIMARY GROUNDING CONDUCTOR WIRE TO BE CONTINUOS AND UNBROKEN/SPLICED. THE SPLICE AT THE GOUND ROD NEAREST THE PANEL IS UNACCEPTABLE.
THE COLD WATER AND GAS PIPES MUST BE BONDED( GROUNDED) THE ELECTRIC SERVICE AND A GROUND JUMPER INSTALLED FROM COLD WATER TO HOT WATER PIPES AT THE WATER HEATER.2) IDENTIFY THE CIRCUITS IN THE PANEL. WHAT AREAS OF THE HOUSE DO THEY SERVE?
08/11/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The service is not per code.| 210*/CORRECTIONS NEEDED:
1)THE ADDRESS NUMBERS MUST BE PERMANENT. USE EMBOSSED METAL STRIP OR OTHER METALLIC, DURABLE, MEDIAL & MUST BE LOCATED ABOVE OR BELOW METER.
2)A COMPLETE NEW GROUNDING SYSTEM, IN COMPLIANCE WITH NEC ART. 250, MUST BE INSTALLED. LEAVE RODS EXPOSED FOR INSPECTION (ENDS W/CLAMP).
RECALL. THANKS.