Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/05/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) BE ADVISED: THE ELECTRICAL EQUIPMENT MANUFACTURER, THE CITY OF TUCSON, TUCSON ELECTRIC POWER, AND THE NEC ART 110, 300, AND 420 PROHIBIT THE USE OF THE SECTION OF PANEL RESERVED FOR THE SERVING UTILITY. FOR CONDUIT ENTRY YOU MUST USE THE LOWER LOAD CENTER AREA. FOR FURTHER CLARIFICATION PLEASE CONTACT MR. RAY MAJUTA, SENIOR ELECTRICAL INSPECTOR AT 791-5550 EXT 1136 2) ARTICLE 250 REQUIRES THE SYSTEM GROUND BE LOCATED NEAREST THE POINT OF SERVICE ENTRANCE. YOUR GROUND RODS SHOULD BE LOCATED IN THE AREA OF THE METER/MAIN/LOAD CENTER 3) PLEASE CORRECT AND RECALL |