Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2004 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* CALL FOR FINAL INSPECTION AFTER TEP TIE IN | |
| 08/13/2004 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1) ADDRESS LABEL TO BE SCREWED OR WIRED TO COVER. 2) SHEET METAL SCREWS NOT TO BE USED FOR GROUND 250-8. 3) PLEAWSE FINISH #4, 6, & 7 OF PREVIOUS INSP. | |
| 08/09/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) A PERMANENT METAL ADDRESS IS NEEDED 2) RISE HARDWARE TO BE 1/4" MINIMUM 3) PLEASE IDENTIFY NEUTRAL CONDUCTOR CLOSER TO WEATHER HEAD 4) GROUNDING ELECTRODE SYSTEM NOT TO BE PARALLELED IF RUN IN METALLIC RACEWAY BOND BOTH ENDS OF RACEWAY 5) SUPPORT CONDUIT TO L3 AND PREVENT DIELECTRIC CONTACT 6) DERATE CONDUCTORS IN CONDUIT TO SUB-PANEL FOR FILL AND HEAT 7) BREAKERS TO BE LISTED FOR USE BY MANUFACTURER 8) PLEASE TIGHTEN GROUND BAR SCREW 9) PROTECT CABLE FROM SHARP METAL EDGES ENTERING JUNCTION BOX 10) PLEASE VERIFY GAS AND WATER BONDS |