Permit: T04EL01559

Parcel: 133124480

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/02/2004 ELECTRIC - FINAL Approved OK TO CLEAR
08/11/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/1)PLEASE FINISH #5 & #7 OF PREVIOUS INSPECTION
08/04/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :CHASE NIPPLE NOT AN APPROVED FITTING FOR USE WITH L.B.
A NEW GROUNDING ELECTRODE SYSTEM IS NEEDED FOR A SERVICE UPGRADE
PLEASE VERIFY GAS AND WATER BONDING
IS FOAM FILL NO COMBUSTIBLE ANF FLAME PROOF
INSTALL ALL STRANDS UNDER TERMINAL LUGS
LOCK NUT MISSTIN ON FITTING
USE CORRECT SIZE BREAKERS FOR CONDUCTOR
A PERMANENT METAL ADDRESS LABEL IS NEEDED
08/02/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :PLEASE LOCK-UP DOORS
07/29/2004 ELECTRIC - FINAL Denied IVRS - Inspection :NO ANSWER AT DOOR, DOG IN YARD