Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04EL01558
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*APPROVED 2035 APPROVED 2091 APPROVED | |
| 08/06/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*1. REMOVE THE THREADED PLUMBING, REDUCING FITTING FROM THE 3/4LB AT SUBPANEL. REPLACE WITH THREADDED NIPPLE AND LOCKNUT. DO NOT USE "CHASE NIPPLES" TO ATTACHE FITTINGS TO PANELS. THE BEVELED SHOULDERS AND "CHASE NIPPLES" DO NOT PROVIDE GOOD GROUNDING CONTACT. 2. ADD A 2ND 2 HOLE STRAP ON MAIN RISER CONDUIT. TEP REQUIRES A "PARAPET ANCHOR". RECALL WHEN CUT-OVER IS COMPLETED. OK TO CLEAR UPGRADE. |