Permit: T04EL01558

Parcel: 125051110


Addresses:

2242 E 4TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04EL01558

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/17/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*APPROVED 2035 APPROVED 2091 APPROVED
08/06/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*1. REMOVE THE THREADED PLUMBING, REDUCING FITTING FROM THE 3/4LB AT SUBPANEL. REPLACE WITH THREADDED NIPPLE AND LOCKNUT. DO NOT USE "CHASE NIPPLES" TO ATTACHE FITTINGS TO PANELS. THE BEVELED SHOULDERS AND "CHASE NIPPLES" DO NOT PROVIDE GOOD GROUNDING CONTACT.
2. ADD A 2ND 2 HOLE STRAP ON MAIN RISER CONDUIT. TEP REQUIRES A "PARAPET ANCHOR".
RECALL WHEN CUT-OVER IS COMPLETED. OK TO CLEAR UPGRADE.