Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/28/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210*/ 1) MURRAY JA220CS NOT ON LIST TO ACCEPT THE CLASSIFIED BREAKER 2) TELEPHONE INTERFACE EQUIPMENT BELOW SERVICE VIOLATES 110.26 3) UPPER COMPONENT FEEDING THRU METER SECTION IS ONLY FOR UTILITY WIRING 4) EXPOSE RODS AND WATER BOND |