Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04EL01507
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/13/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
09/02/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :15 AMPHERE CIRCUITS (#14 WIRE) MUST BE PROTECTED BY 15 AMP CIRCUIT BREAKERS MARK THE CIRCUITS WITH NAME OF AREA THEY SERVE - SUCH AS KITCHEN, BEDROOM, ETC. LITES AND PLUGS NOT ACCEPTABLE MARK THE NEUTRAL CONDUCTOR AT EWATHERHEAD WITH WHITE TAPE OR PAINT WIRE FOR SERVICE MUST BE MARKED SUNLIGHT RESISTANT PROVIDE PIECE WITH THIS MARK |