Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/04/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/30/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection :The service entrance is not per code.| 215* eVERY NEW ELECTRIC SERVICE & UPGRADE REQUIRES A COMPLETE NEW GROUNDING CIRCUIT. yOU MUST INSTALL TWO NEW GROUND RODS AND RUN GROUND WIRE TO COLD WATER AND GAS PIPING EXISTING GROUND IS UNPROVEN LEAVE ROD ENDS EXPOSED FOR INSPECTION THE 2" RISER PIPE MUST HAVE TWO CLAMPS ONE WITHIN 8" OF BOX THE BIRD BOARD IS NON STRUCTURAL DO NOT USE TO CLAMP TO |
|
| 07/23/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |