Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2004 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 09/09/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service entrance is not per code.| 215*/ 1) NEED CORRECTIONS. OWNER TOOK LIST |