Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/06/2004 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 07/30/2004 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection FINISH #3 GAS BOND, #6 SUPPORT CONDUITS AND RISER HARDWARE TO BE 1/4" MINIMUM USE CORRECT STRAPS LB COVER TO BE ACCESSIBLE OK TO COVER GROUND RODS & WIRE |
|
| 07/22/2004 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :A PERMANENT METAL ADDRESS LABEL IS NEEDED A GROUNDING ELECTRODE SYSTEM IS NEEDED GROUND RODS TO BE INSTALLED PER CODE A WATER AND GAD BOND ARE NEEDED USE CORRECT SIZED BREAKER FOR CONDUCTOR AMPACITY MAINTAIN WORKING CLEARANCES IN FRONT AND BELOW SERVICE SUPPORT CONDUITS AS PER CODE JUNCTION BOX TO BE BONDED BLUE WIRE NUTS NOT LISTED FOR USE ABOVE 2-#8 CONDUCTORS CHASE NIPPLE NOT TO AN APPROVED FITTING FOR USE WITH L.B. GROUNDING CONDUCTOR NEEDED FOR NON-METALLIC FLEX |