Permit: T04EL01476

Parcel: 129130800


Addresses:

2032 S PARK AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04EL01476

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/28/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/27/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ 1) SERVICE TO HIGH FROM GROUND LEVEL A MAX HEIGHT OF 6'-7" TO HIGHEST BREAKER 2) GROUND RODS REQUIRED PER 250 NEC. 6' MINIMUM DISTANCE APART 3) BOND GAS PIPING 4) CHASE NIPPLE NOT ALLOWED AT 1" LB ON BOTTOM OF PANEL, MUST BE CLOSE NIPPLE WITH BONDING BUSHING 5) NO PROTECTION FOR CONDUCTORS PASSING THRU BACK OF ENCLOSURE
07/22/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ 1) INSTALL LISTED J-BOX FOR SPLICES AT RIGHT OF SERVICE PANEL. USE PROPER CONNECTORS AND BUSHINGS 2) GROUNDING ELECTRODE CONDUCTOR MUST BE TIED IN TO SERVICE NEUTRAL BAR 3) INSTALL NEW GROUNDING SYSTEM OR VERIFY EXISTING IS INTACT 4) LABEL BREAKERS 5) WORK MUST BE DONE BY C-11 LICENSED CONTR.
07/16/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ 1) ANCHOR SERVICE PANEL TO STRUCTURE, INSTALL PERMANENT LABLE ON COVER, MUST BE SCREWED OR RIVITED 2) SUPPORT CONDUIT 1" PER NEC. WITHIN 3' OF TERMINATION 3) REMOVE 3/4" SEAL TIGHT TIED BETWEEN SERVICES, NOT THAT THERE ARE 2 SERVICES ON BLDG 4) ID NEUTRAL WITH WHITE COLOR CODING TAPE