Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/30/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* |
| 07/23/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :*/ 1) CHASE NIPPLE NOT AN APPROVED FITTING FOR USE WITH RIDGID NIPPLE 2) TIGHTEN SPLIT BOLT 3) FINISH #11 PREVIOUS INSPECTION |
| 07/16/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) STRAP GROUNDING ELECTRODE CONDUCTOR TO BLDG 2) NO ENTRANCE IN TOP AREA BEHIND SHEILD AS PER MANUFACTURER LABEL 3) DERATE CONDUCTORS IN RACE WAY 4) SUPPORT CONDUIT BELOW GUTTER WITHIN 3' 5) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 6) RECEPTACLE COVER TO BE WEATHER PROOF, WEATHER OR NOT PLUGED IN 7) BLUE WIRE NUTS NOT LISTED FOR USE OVER #8 CONDUCTORS 8) PLASTIC BUSHING NEEDED AT FITTINGS FOR CONDUCTORS ? #8 9) ID NEUTRAL CLOSER TO WEATHER HEAD 10) PLEASE SUPPORT GROUND AND CONDUIT ACCROSS ROOF 11) WHAT ARE EXPOSED CONDUCTORS ON ROOF 12) WATER BOND TO BE INTERIOR SIDE OF UNION |