Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04EL01467

Parcel: 127034100


Addresses:

5750 E ROSEWOOD ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/30/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/23/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) CHASE NIPPLE NOT AN APPROVED FITTING FOR USE WITH RIDGID NIPPLE 2) TIGHTEN SPLIT BOLT 3) FINISH #11 PREVIOUS INSPECTION
07/16/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) STRAP GROUNDING ELECTRODE CONDUCTOR TO BLDG 2) NO ENTRANCE IN TOP AREA BEHIND SHEILD AS PER MANUFACTURER LABEL 3) DERATE CONDUCTORS IN RACE WAY 4) SUPPORT CONDUIT BELOW GUTTER WITHIN 3' 5) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 6) RECEPTACLE COVER TO BE WEATHER PROOF, WEATHER OR NOT PLUGED IN 7) BLUE WIRE NUTS NOT LISTED FOR USE OVER #8 CONDUCTORS 8) PLASTIC BUSHING NEEDED AT FITTINGS FOR CONDUCTORS ? #8 9) ID NEUTRAL CLOSER TO WEATHER HEAD 10) PLEASE SUPPORT GROUND AND CONDUIT ACCROSS ROOF 11) WHAT ARE EXPOSED CONDUCTORS ON ROOF 12) WATER BOND TO BE INTERIOR SIDE OF UNION