Permit: T04EL01463

Parcel: 116191360


Addresses:

24 N LINDA AV #02

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
08/02/2004 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
07/30/2004 ELECTRIC - RECONNECT Cancelled IVRS - Ri canceled
07/30/2004 ELECTRIC - RECONNECT Denied IVRS - Inspection :
The service is not per code.| 210*/ 1) INSTALL A NEW 60A MAIN PANEL WITH 60A MAIN CIRCUIT BREAKER TO PROTECT THE CIRCUIT CONDUCTORS FEEDING THE REAR HOUSE. EQUPMENT MUST BE RATED SUITABLE AS SERVICE EQUIPMENT
07/16/2004 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) NEED PLANS AND PERMIT FOR NEW WIRING, PLUMBING AND MECHANICAL 2) BOXES NEED TO BE PROPERLY GROUNDED PER NEC ARTICLE 250 3) SMOK DETECTORS REQUIRED IN ALL SLEEPING AREAS AND HALL 4) HANDY BOXES OVERFILLED 5) SECURE M/C CABLE PER NEC WITHIN 12" OF BOX 6) INSTALL GROUNDING ELECTRODE SYSTEM AT UNIT #2 AND BOND WATER AND GAS 7) INSTALL MAIN BREAKER AT PANEL AND COUPLING NOT APPROVED WHERE SUBJECT TO WEATHER 8) CONDUIT NOT SECURED PER NEC 9) USE ANTI OX PASTE FOR ALUMINIUM WIRE 10) COPPER AND ALUMINIUM CONDUCTORS TO BE PROPERLY TERMINATED 11) REPAIRS TO BE DONE BY A LICSENSED CONTRACTOR TO AVOID DELAY OF APPROVAL