Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T04EL01453

Parcel: 113104230


Addresses:

1719 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T04EL01453

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
07/29/2004 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
07/28/2004 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*/ 1) CABLE TIE WRAPS ARE NOT PERMITTED FOR OUTDOOR USE UNLESS THEY ARE THE BLACK UV SUNLIGHT RESISTANT TYPE. BEST TO USE METAL 3/8" STRAPS 2) INSTALL A PANEL CIRCUIT DIRECTORY 3) SCRAPE PAINT OFF WATER LINE (UNDERGROUND WIRE PIPE CLAMP) 4) AT FIRST GROUND ROD-MOVE GROUND WIRE TO THE POCKET SIDE OF CLAMP 5) CORRECT AND RECALL
07/16/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) USE SQ D BREAKERS IN SQ D PANEL (100 AMP) 2) USE BOND BUSHING AT EMT 1 1/4" CONNECTION AT SERVICE PANEL 3) TIGHTEN CONNECTOR AT PANEL 4) ID NEUTRAL CONDUCTOR AT SERVICE 5) USE 2" IMC OR RIGID RISER 6) INSTALL 2" ROOF JACK AT RISER 7) EXPOSE GROUNDING ELECTRODE SYSTEM AT SERVIVICE AND AT MAIN HOUSE AND BOND WATER AND GAS PIPING PER NEC 250 8) EXPSOE UG FOR DEPTH AND CONDITION OF CONDUIT (EMT NOT ALLOWED FOR UG USE) 9) IDENTIFY ADDRESS ON SERVICE PER T & P 10) RISER HAS NO SUPPORT ?