Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T04EL01453
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2004 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 07/28/2004 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :*/ 1) CABLE TIE WRAPS ARE NOT PERMITTED FOR OUTDOOR USE UNLESS THEY ARE THE BLACK UV SUNLIGHT RESISTANT TYPE. BEST TO USE METAL 3/8" STRAPS 2) INSTALL A PANEL CIRCUIT DIRECTORY 3) SCRAPE PAINT OFF WATER LINE (UNDERGROUND WIRE PIPE CLAMP) 4) AT FIRST GROUND ROD-MOVE GROUND WIRE TO THE POCKET SIDE OF CLAMP 5) CORRECT AND RECALL | |
| 07/16/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) USE SQ D BREAKERS IN SQ D PANEL (100 AMP) 2) USE BOND BUSHING AT EMT 1 1/4" CONNECTION AT SERVICE PANEL 3) TIGHTEN CONNECTOR AT PANEL 4) ID NEUTRAL CONDUCTOR AT SERVICE 5) USE 2" IMC OR RIGID RISER 6) INSTALL 2" ROOF JACK AT RISER 7) EXPOSE GROUNDING ELECTRODE SYSTEM AT SERVIVICE AND AT MAIN HOUSE AND BOND WATER AND GAS PIPING PER NEC 250 8) EXPSOE UG FOR DEPTH AND CONDITION OF CONDUIT (EMT NOT ALLOWED FOR UG USE) 9) IDENTIFY ADDRESS ON SERVICE PER T & P 10) RISER HAS NO SUPPORT ? |