Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/16/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/14/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SEE WRITE UP OF INSPECTIONS DATED 7/9/04 PER E-3 JERRY ORTA FOR ITEMS NEEDING REPAIR. ALSO CORRECT PERMITS FOR OTHER ADDRESSES |
|
| 07/09/2004 | ELECTRIC - FINAL | Denied | 1) HAVE PERMIT ON SITE TO VERIFY 2 OTHER ADDRESSES 2) NEED MAIN BONDING JUMPER FROM GUTTER. NEUTRAL TO GUTTER FRAME 2) PREFER A SPLIT BOLT TOP FOR EACH SERVICE ON GROUNDING ELECTRODE CONDUCTOR RATHER THAN RELYING ON OTHER EQUIPMENT (?) TO BE ACCESSED 3) MAINTAIN THE INTEGRITY OF EACH OCCUPANT HAVING ACCESS TO THEIR OWN SERVICE AND BRANCH CIRCUITS A) DO NOT SPLICE, USE AS PULL BOX ONE APARTMENT INTO ANOTHER APARTMENT SERVICE B) CANNOT HAVE GATED (LOCKABLE) OCCUR INTO SERVICE. ACCESS FOR ALL TENANTS REQUIRED |