Permit: T04EL01423

Parcel: 107051080


Addresses:

2928 N 15TH AV #12

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/07/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/22/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
Install 2 ground rods 6 feet apart with a continuous grounding electrode conn
1) CORRECTIONS REQUIRED: #12 SMOKE DETECTORS (COMPLETE AND OPERABLE) INSIDE EACH BEDROOM AND IN THE HALL/ATRIUM IMMEDIATELY BEFORE THE BEDROOM. COVER OVER PEDESTAL OPEN SPACE
2) #25 50 AMP BREAKER AND 4 PRONG RECEPTACLE PLATE INSTALLED IN PEDESTAL. ADD ONE SMOKE DETECTOR NEAR WEST BEDROOM AND MOVE SMOKE DETECTOR FROM LIVING ROOM AREA TO AREA IMMEDIATELY BEFORE EAST BEDROOM
3) #31 SWITCH OUT THE 30 AMP RECEPTACLE AND BREAKER WITH A 50 AMP SET UP. RE-ARRANGE SMOKE DETECTORS TO BEDROOMS (INSIDE) AND HALL. 3 ALL