Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2006 | ELECTRIC - FINAL | Approved | OK FINAL, RTMAJUTA | |
| 02/01/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* LAP POOL PUMP ROOM. 1) EXTENSION CORD TO BE REMOVED- PERMANTENT MEAN TO CONNECT EQUIPMT TO BE USED. 2) COMPRESSOR CANNOT BE UNDER & IN FRONT OF DISCONNECT FOR PANEL 3) LABEL DISCONNECT & PANEL |
|
| 01/06/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/1)FOUNTAIN & ASSOCIATED EQMT OF FINAL 2)POOL ROOM - PATIO POOLS EQUIPMT. OK EXCEPT J-BOX NORTH WALL - HAS #12 WIRES HANGING OUT - NEED TO BE FINISHED. ID DISCONNECT SWITHCHES PERMANENTLY ALSO IN LAP POOL AREA 3)LAP POOL MUST BE ENERGIZED AND TESTED. OTHER WORK BY OTHER PEOPLE HAS NOT BEEN COMPLETED AND HAS TO BE FINISHED TO FINAL PERMIT. ALL SWITCHED FOR 1 PHASE & 3 PHASE MOTORS OK | |
| 01/05/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ALL MOTORS HAVE TO BE BONDED PATIO MOTORS OK ECO LAB NOT 2) OUTLET BELOW 120/208V PANEL UNFINISHED. 3) RAIN BIRD CABINET NEEDS POWER. 4) MISSING POWER FOR SOME PUMPS (NOT IN ECO LAB) 5) SINGLE POLE DISCONNECTS SWITCHED FOR 208 V MOTORS 1 LEG SWITCHED ONLY-MAY HAVE TO BE 2 POOL 2 THROW.POOL HOUSE OK TEMP SERVICE | |
| 01/01/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |