Permit: T04EL01396

Parcel: 107130400


Addresses:

101 W GLENN ST


Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Permit Number - T04EL01396

Inspection Description - ELECTRIC - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
08/19/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* partial to meet further code requirements you must bond both service enclosures ( panels) to each other
08/10/2004 ELECTRIC - FINAL Denied IVRS - Inspection :(1) NOTE MURRAY DOES NOT ALLOW ANY CONDUIT ENTRIES ON TOP OR AREA WHICH CAN NOT BE REMOVED ONCE METER INSTALLED. (2) STILL CAN NOT LOCATE GAS BOND.
07/07/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) DUE TO THE PANEL CONTAINING 4-2 POLE 30 AMP LOADS, 1-2 POLE 50 AMP LOAD AND 2-20 AMP LOADS SERVICE SHOULD BE 200A 2) CLOSE NIPPLE BETWEEN J-BOX AND SERVICE SHOULD ENTER SERVICE BELOW IN BREAKER AREA BECAUSE TOP HALF OF SERVICE IS LOCKED AND NOT ACCESSIBLE. ALSO CLOSE NIPPLE HAS LOOSE LOCK NUTS 3) JUNCTION BOX HAS 1/2" HOLE 4) CONDUIT FROM J-BOX TO SERVICE 103 SHALL HAVE A NEUTRAL TAPED WHITE SAME SIZE AS HOT'S REMOVE GREEN WIRES 5) INSULATION ON CABLES TO BE TRIMMED AT ENTRY TO BOX. NOTE: OVERHEAD CLEARANCE ON ROOF SUBJECT TO TEP 6) COULD NOT LOCATE GAS BOND 7) GREEN GROUND TO HAVE ALL STRANDS IN TERMINAL ( NOTES FOR 103 GLENN ST: 1) THERE ARE 2-2 POLE 60 AMP BREAKERS, 1-2 POLE 40 AMP BREAKERS, 1-2 POLE 30 AMP BREAKERS, 1-2 POLE 20 AMP BREAKERS AND 1-1 POLE 20 AMP BREAKERS. THIS SHOULD BE A 200 AMP SERVICE 2) NEUTRAL ON 30A 2 POLE MISSING-CANNOT USE GREEN #12 USE #10-WHITE OR TAPED 3) NEUTRAL ON TERMINAL TO HAVE ALL STRANDS IN 4) COULD NOT LOCATE GAS BOND ? 5) CONDUIT ENTRY ON LOCKABLE PART OF SERVICE, SHOULD BE ON CB SIDE 6) OVERHEAD CONDUCTORS SUBJECT TO TEP