Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/20/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/16/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) NOTE: YOU HAVE MAJOR STRUCTURAL CONCERNS ALONG OUTSIDE EAST ADOBE WALL. WE WILL NOT BE ABLE TO RELEASE POWER TILL THIS HAS BEEN ADDRESSED PROPERLY (NOTE-A STRUCTURAL REPAIR PERMIT WILL BE REQUIRED) |
|
| 07/15/2004 | ELECTRIC - FINAL | Denied | 1) MARK SERVICES WITH ADDRESS 2) CHANGE GREEN WIRE USED AS HOT TO BLACK OR RED | |
| 07/14/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) THE SUB PANEL WITH FUSES HAS TO BE REDRESSED, THE TERMINATIONS. HAVE TO BE RE-CLEANED AND RE-TERMINATED. REMOVE DOUBLE LUGGING 2) INSTALL OPEN WIRING IN A COVERED BOX 3) CLEAN AND RETERMINATE SERVICES AND SUB PANEL OUTSIDE 4) IDENTIFY DISCONNECTS BY PERMANENT MEANS |