Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/08/2004 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 07/07/2004 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :*/ 1) SMOKE DETECTORS TO BE 3' FROM A REGISTRAR 2) WHERE IS PREVIOUS INSPECTION REPORT ? | |
| 07/01/2004 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) KITCHEN COUNTER RECEPTACLES REQUIRED TO BE GROUND FAULT TNTERRUPTER PROTECTED GFI TYPE 2) FUSE PANEL IN CLOSET #14 WIRE TO BE FUSED AT 15 AMPS #12 WIRE TO BE FUSED AT 20 AMPS CURRENTLY ALL FUSE 30 AMP AND 25 AMP 3) DOUBLE LUGGING OF CONDUCTORS ON LINE SIDE OF MAIN SERVICE DISCONNECT ILLEGAL-APPEARS THE DRYER RECEPTACLE FEED ADDED WITHOUT INSPECTION 4) THE SERVICE ENTRANCE CABLES EXISTING BELOW 8' TO GROUND NEED TO BE PHYSICALLY PROTECTED 5) THE SERVICE CONDUCTORS AT ROOF ARE CRACKED AND FRAYED AT INSULATION EXPOSING ENERGIZED CONDUCTORS. PLEASE OBTAIN SERVICES OF RESIDENTIAL LICENSED ELECTRICIAN TO CORRECT PROBLEMS AND RECALL FOR RE-INSPECT |