Permit: T04EL01378

Parcel: 116140350

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T04EL01378

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
07/01/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999$/ 1) GAS PIPING BOND REQUIRED-CANNOT LOCATE IT 2) WHEN A SERVICE IS UPGRADED IT IS REQUIRED TO COME UP TO CURRENT CODE. THE HOSE BIB BELOW THE SERVICE IS RIGHT IN FRONT OF THE CIRCUIT BREAKER AREA. 110-26 REQUIRES CLEARANCE IN FRONT OF UP 3' DOWN TO GRADE