Permit: T04EL01350

Parcel: 134241640


Addresses:

641 S KENYON DR

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
07/22/2004 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
07/20/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :DENIED. (1) NEED PERMANENT ADHERE TAG PER CITY AMENDMENT. (2) #4 BARE CU. WIRE CROOKED, PLEASE STRAIGHTEN OUT. (3) NEED TO BOND BOTH ENDS OF CONDIUT EV??SY(?) G??D WIRE.










See detailed listing on site.| 999*
06/29/2004 ELECTRIC - SERVICE UPGRADE Partial Approval NEED PERMANENT ADDRESS LABEL. NEED TO BOND BOTH ENDS OF CONDUIT PROTECTING THE MAIN GROUNDING ELECTRODE CONDUCTOR. LOOSE FITTINGS. NEED ¼" HARDWARE EG: ¼" LUG SCREWS TO SUPPORT RISER. LICENSED CONTRACTOR REQUIRED. PLEASE FIND WHERE SPLICES ARE MADE.