Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/22/2004 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 07/20/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection :DENIED. (1) NEED PERMANENT ADHERE TAG PER CITY AMENDMENT. (2) #4 BARE CU. WIRE CROOKED, PLEASE STRAIGHTEN OUT. (3) NEED TO BOND BOTH ENDS OF CONDIUT EV??SY(?) G??D WIRE. See detailed listing on site.| 999* |
|
| 06/29/2004 | ELECTRIC - SERVICE UPGRADE | Partial Approval | NEED PERMANENT ADDRESS LABEL. NEED TO BOND BOTH ENDS OF CONDUIT PROTECTING THE MAIN GROUNDING ELECTRODE CONDUCTOR. LOOSE FITTINGS. NEED ¼" HARDWARE EG: ¼" LUG SCREWS TO SUPPORT RISER. LICENSED CONTRACTOR REQUIRED. PLEASE FIND WHERE SPLICES ARE MADE. |