Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04EL01346
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/01/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/29/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PLASTIC ANCHORS FOR STRUT SUPPORTING 2" RISER ARE INSUFFICIENT - USE MIN. ΒΌ" STRENGTH. 2) INSTALL COVER ON OPEN BREAKER SLOT. 3) CONDUIT ENTRY IS ABOVE PANEL BUS. - REQUIRES A SEALING LOCK NUT. |