Permit: T04EL01322

Parcel: 115044630

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T04EL01322

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
07/13/2004 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
06/25/2004 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) PANEL IN ALLEY NOT SUPPORTED AND EMT FITTING ON CONDUIT TO METER IS LOOSE. 2) PANEL SCHEDULE STATES ONE 20 AMP CIRCUIT IS FOR APT 7, ANOTHER FOR GARAGE. ONE 20 AMP CIRCUIT IS INSUFFICIENT TO RUN AN ENTIRE APARTMENT WHICH INCLUDES REFRIGERATOR, COOLER, LIGHTING AND POWER. THIS APT. NEEDS TO BE FITTED WITH EXTRA CIRCUITRY. WHAT DOES GARAGE CIRCUIT FEED?