Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/15/2004 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection :* | |
| 07/08/2004 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) CHASE NIPPLES NOT ALLOWED, USE CLOSE NIPPLES WITH LOCKNUTS 2) USE APPROVED WIRE NUTS TO SPLICE GROUND WIRES IN J-BOX, TWISTING WIRES TOGETHER ONLY NOT APPROVED METHOD 3) USE PERMANENT ADDRESS LABEL ON SERVICE, NO MAGIC MARKER 4) GROUND J-BOX, DO NOT USE SHEET METAL SCREW 5) METHOD OF SUPPORTING RISER NOT APPROVED, SUPPORT STRAPS MUST BE SECURED TO STRUCTURE |