Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2005 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 12/08/2004 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :*/1)FILL UNUSED OPENING IN PANEL COVER 2)PLEASE CLEAN SURFACE UNDER GAS BOND CLAMP OF OAINT 3)HIGHEST AVAILIABLE BREAK FOR 6'7" SEE NOTE 3 PREVIOUS INSPECTION *NOTE: FINAL CLEARANCE TO BE MADE BY COMBONATION GENERAL INSPECTOR | |
| 06/24/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PLEASE VERIFY A PERMIT FOR ALL NEW INTERIOR ELECTRIC, PLBG, MECH AND BLDG. 2) ADDRESS LABEL TO BE PERMANENT - METAL. 3) HIGHEST AVAILABLE BREAKER NOT TO BE OVER 6'7" WE HAVE 6'11.5" 4) GROUNDING EQUIPMENT CONDUCTOR SMALLER THAN #8 TO BE GREEN ENTIRE LENGTH. NEUTRAL CONDUCTOR TO BE WHITE ENTIRE LENGTH. 5) PLEASE VERIFY WTR BOND. 6) ON A NEW SERVICE A NEW GROUNDING ELECTRODE SYSTEM IS TO BE INSTALLED - 2 GROUNG RODS. |