Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/01/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/24/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ PLEASE INDICATE WHERE OR EXPOSE GROUND RODS. SERVICE NOT IN COMPLIANCE WITH 99 NEC, 230-72 (C). T.V. CABLE AND TELE. BELOW SERVICE VIOLATES 110-26. |