Permit: T04EL01309

Parcel: 133362760


Addresses:

9922 E 5TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04EL01309

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/01/2004 ELECTRIC - FINAL Approved
08/31/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
06/28/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) INSTALL SPLIT BOLT CORRECTLY TO PREVENT DISSIMALAR METAL CONTRACT. 2) GROUNDING EQUIPMENT CONDUCTORS TO BE EQUIVELNET SIZED. 3) COMPLETE 2, 6 AND 7 OF PREVIOUS INSP.
06/23/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) SEAL ENTRANCES ABOVE CURRENT CARRING PARTS GROUNDS CHASE NIPPLE. 2) USE APPROVED COPPER TO ALUMINUM CONNECTORS. ALSO SIZE HAS TO BE EQUIVELENT TO ORIGINAL CONDUCTOR. 3) SUPPORT CONDUITS ABOVE PANEL. 4) TIGHTEN LOOSE FITTINGS ALSO ON ROOF. 5) A BONDING DEVICE IS NEEDED ON BOTH SIDES OF SERVICE NIPPLE 250-94. 6) CANNOT FIND CONDUCTOR MARKING TO VERIFY SIZE ON SERVICE CONDUCTORS. 310-11. 7) IDENTIFY UNGROUNDED CONDUCTOR ENTIRE EXPOSED LENGTH.