Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04EL01309
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/01/2004 | ELECTRIC - FINAL | Approved | ||
| 08/31/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* |
|
| 06/28/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ 1) INSTALL SPLIT BOLT CORRECTLY TO PREVENT DISSIMALAR METAL CONTRACT. 2) GROUNDING EQUIPMENT CONDUCTORS TO BE EQUIVELNET SIZED. 3) COMPLETE 2, 6 AND 7 OF PREVIOUS INSP. | |
| 06/23/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) SEAL ENTRANCES ABOVE CURRENT CARRING PARTS GROUNDS CHASE NIPPLE. 2) USE APPROVED COPPER TO ALUMINUM CONNECTORS. ALSO SIZE HAS TO BE EQUIVELENT TO ORIGINAL CONDUCTOR. 3) SUPPORT CONDUITS ABOVE PANEL. 4) TIGHTEN LOOSE FITTINGS ALSO ON ROOF. 5) A BONDING DEVICE IS NEEDED ON BOTH SIDES OF SERVICE NIPPLE 250-94. 6) CANNOT FIND CONDUCTOR MARKING TO VERIFY SIZE ON SERVICE CONDUCTORS. 310-11. 7) IDENTIFY UNGROUNDED CONDUCTOR ENTIRE EXPOSED LENGTH. |