Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04EL01302
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/17/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* APPROVED AS PER PREVIOUS INSPECTION | |
06/24/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/ 1) LABEL BREAKERS AT SUB PANEL. 2) A MAIN BREAKER IS NEEDED INSIDE PANEL AS A 2ND STRUCTURE. 3) BOND GROUNDING ELECTRODE CONDUCTOR TO CONDUIT PER CODE. 4) ALSO NEED GROUNDING ELECTRODE SYSTEM AT 2ND STRUCTURE. 5) MULTIWIRE CIRCUIT ON SAME YOKE TO HAVE MANUFACTURERS TIE HANDLE. OK TO BACKFILL AND COVER TRENCH. |