Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/08/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection :* |
| 07/06/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection :*/ 1) MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE 110-26 PLANTS AND REGISTRATION 2) SEAL UNUSE OPENINGS IN PANEL 3) SPLIT BOLT LISTED FOR ONLY 2 CONDUCTORS-A RUN AND A TAP 4) BLUE WIRE NUTS NOT LISTED FOR LARGER THAN #8 CONDUCTORS 5) GREEN CONDUCTOR NOT TO BE WHITE AND TO BE GREEN ENTIRE LENGTH 250-119 AND 200-7 |