Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T04EL01273

Parcel: 12108001B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04EL01273

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/01/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*/ 1) OK FINAL THIS PERMIT
06/30/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) BOND JUNCTION BOXES PER 250-148 2) SUPPORT WIRES FOR TRACK LIGHTING TO BE #12 MINIMUM 3) OTHER PERMIT NEEDS TO BE CALLED IN FOR C OF O