Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*/APPROVED | |
| 07/16/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) THESE LIGHTS DO NOT MEET THE CITY OF TUCSON-PIMA COUNTY LIGHT POLLUTION ORDINANCE 2) SPACE A8'S (B12, C11 LIGHT FIXTURE HAS EXPOSED N.M. CABLE (NOT SUNLIGHT RESISTANT AND WILL END UP DETERIORATING IN HTE SUN. THIS IS A POSSIBLE FUTURE SHOCK HAZZARD IF NOT ADDRESSED AT THIS TIME) C9 EMT IN CONTACT WITH SOIL (THIS WILL RUST THROUGH IF NOT CORRECTED) |