Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/19/2004 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* CALL FOR FINAL ONCE CHANGED OVER. LETTER PER LIC ELECT CONTRACTOR L-11 198634 C-11 198635 | |
| 07/12/2004 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) REGISTRAR OF CONTRACTORS-FARWEST PUMP COMPANY DOES NOT HAVE A RESIDENTIAL LICENSE |
|
| 07/07/2004 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SERVICE REQUIRED TO HAVE A PERMANENT ADDRESS LABEL (METAL AND SCREWED OR RIVIT ON) 2) NEED A SUPPORT ON 2" RISER BELOW ROOF LINE 3) ON A SERVICE UPGRADE-NEW GROUNDING SYSTEM REQUIRED INCLUDING 2 GROUND RODS 6' APART, WATER AND GAS LINE BONDS 4) LOCK NUTS, ON RIGHT SIDE OF PANEL-TIPS TO BE REVERSED SO TIPS GRIP ENCLOSURE, ENTRYS ABOVE BUS REQUIRE SEALING LOCK NUTS 5) TEMP NEUTRAL TIE INTO BOX TO BE INDENTIFIED WHITE (TAPE). NAME LICENSED CONTRACTOR PRIOR TO NEXT INSPECTION |