Permit: T04EL01262

Parcel: 119044590

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/20/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/16/2004 ELECTRIC - FINAL Partial Approval
07/15/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*PARTIAL APPROVAL, (1) PVC EXPOSED MUST BE SCH. 80 PER COT ORDINANCE. (2) SUPPORT PVC CONDUIT PER CODE.
07/14/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ 1) SERVICE TO UNIT #1 ON SOUTH END OF BLDG NOT KNOWN AT FIRST INSPECTION. SERVICE IN NEED OF REPAIR FUSED DISCONNECT NEEDS TO BE REPLACED, OLD ROMEX, J-BOX NOT APPROVED FOR OUTDOOR USE. INSULATOR AT SERVICE DROP PULLED OUT
06/16/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ UNIT 1 - 1) OVERSIZED MAIN BREAKER AT SERVICE. 2) OVERSIZED FUSES IN SUB-PANEL. INSTALL PROPER SIZED FUSES FOR WIRE SIZE, INSTALL TAMPER INSERTS TO PREVENT OVERFUSING. 3) UNGROUND SYSTEM CANNOT HAVE GROUNDED RECEPTS UNLESS A GFCI RECEPT AHEAD OF CIRCUIT. 4) INSTALL W/P RECEPTS AND COVER FOR COOLER. 5) MURCURY VAPOR LIGHT OUTSIDE NOT ALLOWED PER COT LIGHTING ORD. / UNIT 3 - 1) SUPPORT 240V OUTLET IN KITCHEN. / UNIT 6 - ROMEX WIRING MUST BE IN RACEWAY WHERE EXPOSED. OK TO CLEAR UNITS 2, 4, 5.