Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/07/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/02/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) INSTALL MISSING FIXTURES 2) SMOKE DETECTORS MUST BE 3' AWAY FROM AC REGISTERS 3) TERMINATE ROMEX INTO J-BOX AT FRONT PORCH LIGHT 4) COVER EXPOSED ROMEX IN STORE ROOM |
|
| 06/11/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*. Called phone 370-8934 spoke to owners rep. someone was to be here to meet inspector 9-10 am, no one here. Install smoke detectors in bedrooms. Romex wiring in store room must be protected below 8', install drywall on walls or raceway. install permanent address label on service, must be screwed or rivited to cover. Missing light fixture in washroom. motion light in carport not wired correctly, must have approved box behind fixture. Replace or repair broken outside entry light fixture at front door. Recall when done. Use C-11 licensed contr. |