Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2004 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 07/07/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SERVICE REQUIRED TO HAVE A METAL ADDRESS TAG SCREWED ON 2) SERVICE HAS TO HAVE A CLEARNACE BELOW IT AND 3' OUT-THE COMPRESSOR IS IN THE WAY 3) RISER ABOVE ROOF NEEDS A KICKER SUPPORT BEHIND IT 4) UPGRADES IN SERVICE REQUIRE NEW GROUNDING SYSTEMS, WHICH WOULD BE YOUR GROUND RODS WITH AN UNSPLICED WIRE TO SERVICE. ALSO NEED A WATER BOND AS WELL AS GAS BOND 5) THE 2" OFFSET NIPPLE REQUIRES GROUNDING BUSHINGS BECAUSE IT CARRIES UNPROTECTED CONDUCTORS AND ENTERS THRU CONCENTRIC KNOCKOUTS |