Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/21/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/10/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SERVICE #3 CANNOT USE GREEN WIRES AS HOTS. 2) IN GUTTER UNPROTECTED CONDUCTORS TO HAVE GROUNDING BUSHINGS WITH A JUMPER TO ENCLOSURE 250-94 NEC. 3) USE A ROMEX CONNECTOR ON BOTTOM OF ENCLOSURE TO SEAL OPENING AROUND GROUND WIRE. |