Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/05/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 08/04/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 08/04/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/11/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) RISER CROOKED. 2) WTR BOND CONNECTION IS ISOLATED BY WTR HTR AND DIELECTRIC UNION. 3) TOP METER SECTION IS NOT A READILY ACCESSABLE AREA. PREMISES WIRING NOT TO ENTER THIS AREA. 4) NEED INTERIOR ACCESS - NEED TO SEE OTHER END TERMINATION OF CIRCUIT. 5) PLEASE HIGHLIGHT THE PANEL BOARD LISTING. 6) NEED CLEAR WORKING SPACE ABOUT ELECTRICAL EQUIPMENT BELOW AND ABOVE SERVICE FROM FOREIGN PIPING AND SYSTEM. |