Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/16/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/05/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/04/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/04/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/11/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) RISER CROOKED. 2) WTR BOND CONNECTION IS ISOLATED BY WTR HTR AND DIELECTRIC UNION. 3) TOP METER SECTION IS NOT A READILY ACCESSABLE AREA. PREMISES WIRING NOT TO ENTER THIS AREA. 4) NEED INTERIOR ACCESS - NEED TO SEE OTHER END TERMINATION OF CIRCUIT. 5) PLEASE HIGHLIGHT THE PANEL BOARD LISTING. 6) NEED CLEAR WORKING SPACE ABOUT ELECTRICAL EQUIPMENT BELOW AND ABOVE SERVICE FROM FOREIGN PIPING AND SYSTEM.