Permit: T04EL01215

Parcel: 123053060


Addresses:

2249 E EDISON ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/14/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*/ OK TO CLEAR FINAL. PLEASE STRAP GROUND WIRES BELOW SERVICE AND TO GAS METER TO WALL SO THEY CANNOT BE PULLED OUT.
06/09/2004 ELECTRIC - FINAL Denied 1) THE SUPPORTS ON RISER BELOW ROOF HAVE TO BE MIN. ¼" STRONG - SHEET MEATL SCREWS INSUFFICIENT. 2) NEW SERVICE REQUIRES A NEW GROUNDING SYSTEM. TWO GROUND RODS 6' APART PLUS A GROUND BOND TO GAS AND WTR SYSTEMS. 3) ROOF JACK TO BE SEALED. 4) ALL WHITE CONDUCTORS USED AS HOT TO BE TAPED BLK OR RED. 5) ALUMINUM GROUND WIRES TO BE TIED TO GROUND BUS. 6) CHASE NIPPLE NOT LISTED FOR CONNECTION FROM ENCLOSURE TO LB. MUST BE A CLOSED NIPPLE WITH LOCK NUTS. 7) WTR HTR DISCONNECT CANNOT BE ABOVE WH/ MUST HAVE 3' CLEARANCE IN FRONT OF TO GROUND.