Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/16/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/14/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SERVICE RISER TO BE OF SUFFICIENT HEIGHT 99 NEC 230-24 CLEARANCES OVER ROOFS TO BE 8' ABOVE ROOF. ALSO CHECK WITH TEP - THEY ALSO HAVE REQUIRED CLEARANCES ABOVE ROOFS. ALSO LB SHOULD BE OF A LOCKABLE ENCLOSURE PER TEP SPEC. 2) WHERE IS PERMIT FOR 911? 3) 230-72 OF 99 NEC REQUIRES THE SERVICES OF ONE DROP TO BE GROUNDED. |