Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 07/06/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) REPLACE DAMAGED SEALING LOCK NUT AT METER BASE |
|
| 06/25/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210*/ NEED GROUNDING BUSHING AND BOND JUMPER BOTH SIDES OF NIPPLE AT SERVICE EQUIPMENT. INSTALL NEUTRAL KIT - PER LISTING - AT MAIN DISCONNECT AND RUN NEUTRAL TO THIS BONDED POINT. PERM. MARK ALL DISCONNECTS. DOUBLE LUGGING AT THE X-O OF TRANS. NEED MAIN BREAKER RETAINER AT SUB PANEL. COMPLETE ALL. OTHER ITEMS MAY BE WRONG - NOT A COMPLETE LIST. |