Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/17/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*/ 1) OK TO CLEAR RECONNECT #118 | |
| 06/11/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*. Exposed wiring not per code, thru-out romex in wood studs. Water heater has no disconnect switch, romex not supported. PVC conduit and recepts not supported, also boxes not supported. Make corrections and recall inspection. Use only L-11 licensed contr. to do work |