Permit: T04EL01192

Parcel: 122140110

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04EL01192

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/22/2004 ELECTRIC - FINAL Approved IVRS - Inspection :* OK TO CLEAR SERVICES 1388, 1390, 1390 M5. ALL THESE ADDRESSES ARE ON THE PERMIT UNDER "LOCATION".
07/01/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) GROUND BUSHINGS REQUIRED IN GUTTER 1 1/4" ENTRIES BECAUSE OF UNPROTECTED CONDUCTORS-STANDARD LOCK NUTS INSUFFICENT 250-94 2) GAS BOND REQUIRED ON HOUSE SIDE 3) NEW CIRCUITS WIRED TO INSIDE NOT PERMITTED NOR INSPECTED 4) HOUSE METER WIRING TO BE INSPECTED INSIDE BEFORE REVERSE OR METER, UNIT INSIDE GUTTED-OWNER NEED APPROVED PLAN FOR LAUNDRY