Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/01/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) THE 1 1/4" ENTRY INTO GUTTER ABOVE SERVICE REQUIRES A GROUND BUSHING AND TIE TO ENCLOSURE BECAUSE OF UNPROTECTED CONDUCTORS 250-94 2) THERE ARE NEW ROMEX BRANCH CIRCUITS PULLED INTO APT-THESE HAVE NOT BEEN PERMITTED. FOR FUTURE REFERENCE THE LOCABLE COMPARTMENTS OF A SERVICE SUCH AS TOP 1/2 OF ENCLOSURE, SEALED BY TEP CANNOT BE USED FOR BRANCH CIRCUITS |