Permit: T04EL01191

Parcel: 122140110

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04EL01191

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/22/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/01/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) THE 1 1/4" ENTRY INTO GUTTER ABOVE SERVICE REQUIRES A GROUND BUSHING AND TIE TO ENCLOSURE BECAUSE OF UNPROTECTED CONDUCTORS 250-94 2) THERE ARE NEW ROMEX BRANCH CIRCUITS PULLED INTO APT-THESE HAVE NOT BEEN PERMITTED. FOR FUTURE REFERENCE THE LOCABLE COMPARTMENTS OF A SERVICE SUCH AS TOP 1/2 OF ENCLOSURE, SEALED BY TEP CANNOT BE USED FOR BRANCH CIRCUITS