Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/04/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/01/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) ADDRESS SERVICE. 2) ADD TWO GROUND RODS - NEW SERVICE. 3) STRAP 3/4" EMT TO A/C WITHIN 3' OF SERVICE. 4) GROUND BUSHING AT OFFSET NIPPLE COMING OUT OF METER TO PANEL - BECAUSE OF UNPROTECTED CONDUCTORS. 5) USE ROMEX CLAMP WHERE GROUNDS EXIT BOTTM OF PANEL. 6) STRAP ½" CONDUIT COMING INTO TOP OF PANEL AND BOTTOM. 7) STRAP GROUND WIRES. |