Permit: T04EL01135

Parcel: 136052150


Addresses:

9018 E 33RD PL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/04/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/01/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) ADDRESS SERVICE. 2) ADD TWO GROUND RODS - NEW SERVICE. 3) STRAP 3/4" EMT TO A/C WITHIN 3' OF SERVICE. 4) GROUND BUSHING AT OFFSET NIPPLE COMING OUT OF METER TO PANEL - BECAUSE OF UNPROTECTED CONDUCTORS. 5) USE ROMEX CLAMP WHERE GROUNDS EXIT BOTTM OF PANEL. 6) STRAP ½" CONDUIT COMING INTO TOP OF PANEL AND BOTTOM. 7) STRAP GROUND WIRES.