Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/30/2004 | ELECTRIC - FINAL | Approved | 1) OK TO CLEAR INCREASE | |
| 06/24/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*/ EXPOSED GROUND WIRE ON TOP OF SLAB. WTR BOND TO BE ATTACHED TO HOUSE SIDE OF DIELECTRIC UNION. | |
| 06/22/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ EXPOSE GROUND RODS - TWO REQUIRED 6' APART. INSTALL PERM ADDRESS LABEL ON SERVICE, MUST BE SCREWED OR RIVITED TO COVER. |